Q.11 Medium Power Systems
A transmission line is protected by a distance relay set with Zone 2 reach at 80% of line length. If the line is 150 km and has impedance of 0.4 Ω/km, what is the Zone 2 reach impedance?
A 36 Ω
B 42 Ω
C 48 Ω
D 60 Ω
Correct Answer:  C. 48 Ω
EXPLANATION

Total line impedance = 150 × 0.4 = 60 Ω. Zone 2 reach = 80% × 60 = 48 Ω

Test
Q.12 Medium Power Systems
In selective coordination of protective devices, what is the minimum time interval required between the operation of primary and backup fuses as per Indian standards?
A 0.1 seconds
B 0.2 seconds
C 0.5 seconds
D 1.0 seconds
Correct Answer:  C. 0.5 seconds
EXPLANATION

IS 1885 and IEEE standards recommend a minimum coordination time interval of 0.5 seconds between protective device operations to ensure selectivity.

Test
Q.13 Medium Power Systems
A STATCOM (Static Synchronous Compensator) is installed in a 220 kV network. In what mode should it operate to provide reactive power support during a voltage sag?
A Current source mode (capacitive)
B Voltage source mode (inductive)
C Current source mode (inductive)
D Voltage source mode (capacitive)
Correct Answer:  D. Voltage source mode (capacitive)
EXPLANATION

During voltage sag, STATCOM operates as a voltage source injecting capacitive reactive power (leading current) to support and restore the system voltage.

Test
Q.14 Medium Power Systems
In a multi-machine power system stability study, which parameter is used to measure relative rotor angle instability between two generators?
A Rotor speed deviation
B Rotor angle difference
C Voltage regulation
D Power factor angle
Correct Answer:  B. Rotor angle difference
EXPLANATION

The stability of a multi-machine system depends on relative rotor angles between machines. Loss of synchronism occurs when relative rotor angle exceeds critical limits.

Test
Q.15 Medium Power Systems
A 50 MW, 11 kV, 50 Hz synchronous generator has an inertia constant H = 6 seconds. Calculate the kinetic energy stored in the rotor at rated speed.
A 150 MJ
B 300 MJ
C 600 MJ
D 1200 MJ
Correct Answer:  B. 300 MJ
EXPLANATION

KE = H × S where S = rated MVA. KE = 6 × 50 = 300 MJ. (H is defined as H = KE/MVA)

Test
Q.16 Medium Power Systems
In the Indian power system, the frequency regulation bandwidth for Load Frequency Control (LFC) is typically maintained within:
A ±0.2 Hz from 50 Hz nominal
B ±0.5 Hz from 50 Hz nominal
C ±1.0 Hz from 50 Hz nominal
D ±2.0 Hz from 50 Hz nominal
Correct Answer:  A. ±0.2 Hz from 50 Hz nominal
EXPLANATION

As per CEA guidelines and recent Grid Code specifications, LFC keeps the system frequency within ±0.2 Hz of 50 Hz nominal frequency to ensure quality power supply.

Test
Q.17 Medium Power Systems
A capacitor bank rated 50 MVAR at 400 kV is to be switched in a power system. Which device is most suitable for controlled switching to avoid transient overvoltages?
A Simple circuit breaker
B Synchro-check relay with circuit breaker
C Pre-insertion resistor (PIR) or reactor
D Isolator switch
Correct Answer:  C. Pre-insertion resistor (PIR) or reactor
EXPLANATION

Pre-insertion resistors and reactors limit the inrush current and transient overvoltages when capacitor banks are switched, ensuring smooth energization.

Test
Q.18 Medium Power Systems
Which protection scheme is mandated for inter-state transmission lines in India according to Grid Code 2023?
A Only distance protection
B Distance protection with differential backup
C Differential protection with distance backup
D Overcurrent protection with distance backup
Correct Answer:  C. Differential protection with distance backup
EXPLANATION

Indian Grid Code 2023 requires differential protection as primary with distance protection as backup for critical transmission lines to ensure faster fault clearance.

Test
Q.19 Medium Power Systems
A synchronous generator has a subtransient reactance (X''d) of 0.15 pu and transient reactance (X'd) of 0.25 pu. During a three-phase fault, which reactance is used for the initial fault current calculation?
A Synchronous reactance (Xd)
B Transient reactance (X'd)
C Subtransient reactance (X''d)
D Negative sequence reactance (X2)
Correct Answer:  C. Subtransient reactance (X''d)
EXPLANATION

Subtransient reactance X''d represents the initial response of the generator to a sudden disturbance and is used for calculating the first few cycles of fault current.

Test
Q.20 Medium Power Systems
In a 400 kV transmission line, if the sending end voltage is 400 kV and receiving end voltage drops to 380 kV, what is the percentage voltage regulation?
A 5%
B 4.76%
C 5.26%
D 4.5%
Correct Answer:  C. 5.26%
EXPLANATION

Voltage regulation = [(VS - VR) / VR] × 100 = [(400 - 380) / 380] × 100 = 5.26%

Test